Refined by
Hide irrelevant options
Product Category
Product Group
Colour
Nominal cross section conductor
Max. conductor temperature
Packaging
Material insulation
Conductor Surface
Core insulation material
Core colour
Colour outer sheath
Outer diameter approx.
Low smoke (according to BS EN 61034-2)
Min. permitted bending radius, stationary application/permanent installation
Diameter conductor
Nominal voltage
Trademark
Show all filters
Hide all filters
- Total: 10
RQ (H05Z-K, H07Z-K) - Drum
RQ_Trumma_vp
Used as connectors line and installation line.
Structure
Conductors: Bare stranded copper
Conductor Insulation: Halogen free polymer blends
Core identification: The table below
Technical data:
Rated voltage:
H05Z-K 0.5-1.0 mm²: 300/500
VH07Z-K 1.5-120 mm²: 450/750 V
Test voltage:
H05Z-K 0.5-1.0 mm²: 2000
VH07Z-K 1.5-120 mm²: 2500 V
Max operating temperature +70ºC (+158ºF) H05Z-K
Max operating temperature +90ºC (+194ºF) H07Z-K
Can handle a short operating temperature of +250ºC (+482ºF)
Minimum bend radius: 12 x cable diameter
Packaging
Drum: 500 m 95.0 mm²
- Number of cores:
- 1 .
- Material core insulation:
- Other
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Black
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -15-90 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 90 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black
- Material insulation:
- Polymen
- Operating temperature:
- -5-90 °C
- Core colour:
- Black
- Conductor surface:
- Bare
- Halogen free:
- Yes
- Packaging:
- Drum
- Min. permitted bending radius, stationary application/permanent installation:
- 36.76-63.44 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- No
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RQ (H05Z-K, H07Z-K) - Box
RQ_kartong_vp
Used as connectors line and installation line.
Structure
Conductors: Bare stranded copper
Conductor Insulation: Halogen free polymer blends
Core identification: The table below
Technical data:
Rated voltage:
H05Z-K 0.5-1.0 mm²: 300/500
VH07Z-K 1.5-120 mm²: 450/750 V
Test voltage:
H05Z-K 0.5-1.0 mm²: 2000
VH07Z-K 1.5-120 mm²: 2500 V
Max operating temperature +70ºC (+158ºF) H05Z-K
Max operating temperature +90ºC (+194ºF) H07Z-K
Can handle a short operating temperature of +250ºC (+482ºF)
Minimum bend radius: 12 x cable diameter
Packaging
Box: RQ 0.5-6.0 mm²
- Number of cores:
- 1 .
- Material core insulation:
- Other
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Blue, Brown, Yellow, Grey, Green, Orange, Red, Black, White, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -15-90 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 70-90 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 300-600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Green, Grey, Orange, Yellow, Green/yellow, Brown, Red, White, Blue, Pink, Purple, Light blue, Dark blue
- Material insulation:
- Polymen
- Operating temperature:
- -5-90 °C
- Core colour:
- Blue, Brown, Yellow, Grey, Green, Green/yellow, Purple, Orange, Pink, Red, Black, White
- Conductor surface:
- Bare, Tinned
- Halogen free:
- Yes
- Packaging:
- Carton (box)
- Min. permitted bending radius, stationary application/permanent installation:
- 10.4-19 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- No
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RQ (H05Z-K, H07Z-K) - Ring
71201
Used as connectors line and installation line.
Structure
Conductors: Bare stranded copper
Conductor Insulation: Halogen free polymer blends
Core identification: The table below
Technical data:
Rated voltage:
H05Z-K 0.5-1.0 mm²: 300/500
VH07Z-K 1.5-120 mm²: 450/750 V
Test voltage:
H05Z-K 0.5-1.0 mm²: 2000
VH07Z-K 1.5-120 mm²: 2500 V
Max operating temperature +70ºC (+158ºF) H05Z-K
Max operating temperature +90ºC (+194ºF) H07Z-K
Can handle a short operating temperature of +250ºC (+482ºF)
Minimum bend radius: 12 x cable diameter
Packaging
Plastic coil: RQ 10.0-50.0 mm²
Box: RQ 0.5-6.0 mm²
Drum: 500 m 95.0 mm²
- Number of cores:
- 1 .
- Material core insulation:
- Other
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Blue, Brown, Grey, Red, Black, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -15-90 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 90 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Grey, Green/yellow, Brown, Red, Light blue
- Material insulation:
- Polymen
- Operating temperature:
- -5-90 °C
- Core colour:
- Blue, Brown, Grey, Green/yellow, Red, Black
- Conductor surface:
- Bare
- Halogen free:
- Yes
- Packaging:
- Ring, Carton (box)
- Min. permitted bending radius, stationary application/permanent installation:
- 25.04-63.44 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- No
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RADOX 125 - Spool
RADOX_125_100m
Halogen free flexible connector cable for the internal wiring in lamps, heaters, electrical equipment, command and control cabinets, and in the construction industry. Ideal for the installation inside the tubes as well as for external installation.
Very good electrical and mechanical properties. Wide temperature range and high resistance to oils, ozone, hydrolysis and mechanical stress. Connection wire is flame retardant, at fire it develops minimum of smoke and no corrosive gases are released.
- Number of cores:
- 1 .
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Blue, Brown, Yellow, Grey, Green, Orange, Red, Black, White, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -55-145 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 125 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Green, Grey, Orange, Yellow, Green/yellow, Brown, Red, White, Blue, Purple
- Material insulation:
- Polyolefin (POE)
- Operating temperature:
- -40-125 °C
- Core colour:
- Blue, Brown, Yellow, Grey, Green, Green/yellow, Purple, Orange, Red, Black, White
- Conductor surface:
- Tinned
- Halogen free:
- Yes
- Packaging:
- Spool HS150, Spool HS151, Spool HS200
- Min. permitted bending radius, stationary application/permanent installation:
- 4.35-20.25 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RADOX 125 - Drum
141601
Halogen free flexible connector cable for the internal wiring in lamps, heaters, electrical equipment, command and control cabinets, and in the construction industry. Ideal for the installation inside the tubes as well as for external installation.
Very good electrical and mechanical properties. Wide temperature range and high resistance to oils, ozone, hydrolysis and mechanical stress. Connection wire is flame retardant, at fire it develops minimum of smoke and no corrosive gases are released.
- Number of cores:
- 1 .
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Red, Black, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -55-145 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 125 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Green/yellow, Red
- Material insulation:
- Polyolefin (POE)
- Operating temperature:
- -40-125 °C
- Core colour:
- Green/yellow, Red, Black
- Conductor surface:
- Tinned
- Halogen free:
- Yes
- Packaging:
- Drum
- Min. permitted bending radius, stationary application/permanent installation:
- 25.5-73.5 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RADOX 125 - Conipack
RADOX_125_CK_vp
Halogen free flexible connector cable for the internal wiring in lamps, heaters, electrical equipment, command and control cabinets, and in the construction industry. Ideal for the installation inside the tubes as well as for external installation.
Very good electrical and mechanical properties. Wide temperature range and high resistance to oils, ozone, hydrolysis and mechanical stress. Connection wire is flame retardant, at fire it develops minimum of smoke and no corrosive gases are released.
Structure:
Conductor: Tinned stranded copper acc. to IEC 60228 class 5
Conductor insulation: RADOX 125 (polyolefin)
Sheath Colour: See product data below
- Number of cores:
- 1 .
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Blue, Brown, Grey, Black, White, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -55-145 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 125 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Grey, Yellow, Brown, White, Blue
- Material insulation:
- Polyolefin (POE)
- Core colour:
- Blue, Brown, Green/yellow, Black, White
- Conductor surface:
- Tinned
- Halogen free:
- Yes
- Packaging:
- CK
- Min. permitted bending radius, stationary application/permanent installation:
- 6.75 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
RADOX 125 - Industry Spool
RADOX_125_Industribobin_vp
Halogen free flexible connector cable for the internal wiring in lamps, heaters, electrical equipment, command and control cabinets, and in the construction industry. Ideal for the installation inside the tubes as well as for external installation.
Very good electrical and mechanical properties. Wide temperature range and high resistance to oils, ozone, hydrolysis and mechanical stress. Connection wire is flame retardant, at fire it develops minimum of smoke and no corrosive gases are released.
- Number of cores:
- 1 .
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Blue, Brown, Yellow, Grey, Green, Orange, Red, Black, White, Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Permitted cable outer temperature after assembling without vibration:
- -55-145 °C
- Conductor material:
- Copper
- Twisted cores:
- No
- Max. conductor temperature:
- 125 °C
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Nominal voltage:
- 600 V
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Single insulated/Double insulated:
- Single insulated
- Colour:
- Black, Green, Grey, Orange, Yellow, Green/yellow, Brown, Red, White, Blue
- Material insulation:
- Polyolefin (POE)
- Operating temperature:
- -40-125 °C
- Core colour:
- Blue, Brown, Yellow, Grey, Green, Green/yellow, Orange, Red, Black, White
- Conductor surface:
- Tinned
- Halogen free:
- Yes
- Packaging:
- Spool HS150, Spool HS400, Spool HS200
- Min. permitted bending radius, stationary application/permanent installation:
- 4.35-10.05 mm
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
- Availability:
-
Yes
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Other
- Flame retardant:
- According to IEC/EN 60332-1-2
- Conductor material:
- Copper
- Twisted cores:
- No
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Core colour:
- Green/yellow
- Conductor surface:
- Tinned
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
- Availability:
-
No
- Material core insulation:
- Polyolefin
- Specification core insulation:
- Other
- Core identification:
- None
- Protective conductor:
- No
- Material outer sheath:
- None
- Specification material outer sheath:
- Other
- Colour outer sheath:
- Red
- Flame retardant:
- According to IEC/EN 60332-1-2
- Conductor material:
- Copper
- Twisted cores:
- No
- Screen:
- No
- Protective barrier:
- N/A
- Armouring/reinforcement:
- None
- Insulation integrity:
- N/A
- Drain wire:
- No
- Halogen free:
- Yes
- Conductor category:
- Class 5 = flexible
- Core colour:
- Red
- Conductor surface:
- Tinned
- Reaction-to-fire according to EN 13501-6: Class:
- Eca
- Reaction-to-fire according to EN 13501-6: Smoke production:
- N/A
- Reaction-to-fire according to EN 13501-6: Flaming droplets/particles:
- N/A
- Reaction-to-fire according to EN 13501-6: Acidity:
- N/A
- Low smoke (according to EN 61034-2):
- Yes
- Low temperature resistant (according to EN 60811-504+505+506):
- No
- Oil resistant according to EN IEC 60811-404:
- No
- Total: 10